JB2S-A2-LA-00-D-A-06-30-2 by Eaton Corporation - Receive a Competitive Quote
Part Number: JB2S-A2-LA-00-D-A-06-30-2 | Alternate P/N: JB2SA2LA00DA06302 | Manufacturer: Eaton Corporation | NSN : 5925-01-324-9473 | Item Name : Circuit Breaker | CAGE Code: 74193 | FSC : 5925 Circuit Breakers | ||
We’re excited to announce that JB2S-A2-LA-00-D-A-06-30-2 NSN part is now available and ready for immediate shipping. Part number JB2S-A2-LA-00-D-A-06-30-2 is a Circuit Breaker manufactured by Eaton Corporation with NSN 5925013249473. Are you interested in a quick and competitive quote for this part?
Just NSN Parts, owned and operated by ASAP Semiconductor, is a leading distributor of NSN (National Stock Number) parts, new and obsolete. Because of our dedication to quality, we’re the only independent distributor in the United States with a strict No China Sourcing Pledge. We’re also an AS9120B, ISO 9001:2015 certified, and FAA AC 0056B accredited member of the Aviation Suppliers Association (ASA). Our vast and comprehensive inventory of over 2 billion parts coupled with our shipping facilities in Washington, Oregon, California, New Maxico, Nevada, Arizona, Illinois, Minnesota, Pennsylvania, and New York, allow us to offer you some of the fastest delivery times in the industry.
If you’d like to learn more about NSN part number JB2S-A2-LA-00-D-A-06-30-2 Circuit Breaker, feel free to call us at our toll-free number, +1-714-705-4780, or email us at sales@justnsnparts.com. And, if you’d like to stay informed on new inventory or any promotions, feel free to download the ASAP Semiconductor App from Google Play or the App Store.
NSN Information for Part Number JB2S-A2-LA-00-D-A-06-30-2 with NSN 5925-01-324-9473, 5925013249473
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-01-324-9473 Item PartTypeName: CIRCUIT BREAKER | 5925 | 013249473 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | A | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
JB2S-A2-LA-00-D-A-06-30-2 | 5 | 9 | 3 |
Characteristics Data of NSN 5925-01-324-9473, 5925013249473
MRC | Criteria | Characteristic |
---|---|---|
ADAT | BODY WIDTH | 1.490 INCHES MINIMUM AND 1.510 INCHES MAXIMUM |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM |
AEGJ | SWITCH CONTACT ARRANGEMENT | SINGLE POLE,DOUBLE THROW |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 CLIP |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE AND TWO LINKED |
CPRZ | AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 ALARM |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 2.000 MINIMUM AT 200 PCT AND 20.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 4 QUICK DISCONNECT,MALE |
AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
ADAQ | BODY LENGTH | 2.588 INCHES MINIMUM AND 2.608 INCHES MAXIMUM |
AKPX | POLE QUANTITY | 2 |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 30.0 AMPERES AC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 2 TOGGLE |
CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
CRTK | SWITCH TERMINAL TYPE | TAB,SOLDER LUG |
CSSX | SWITCH CURRENT RATING AND TYPE IN AMPS | 10.0 AC |
CWJK | CASE MATERIAL | PLASTIC |
ADAU | BODY HEIGHT | 1.920 INCHES MINIMUM AND 1.940 INCHES MAXIMUM |
AJEC | BOSS HEIGHT | 0.125 INCHES MINIMUM AND 0.317 INCHES MAXIMUM |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
FREQ | FREQUENCY IN HERTZ | 50.0 OR 60.0 ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CQSM | SWITCH LOCATION AND POSITION DESIGNATION | EXTERNAL AT POLE ONE |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF AND FUNGUS PROOF |
CSWP | SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 250.0 AC |