If you are seeking purchasing solutions on reliable parts with the NSN 5925-01-300-8939, your needs are covered here on Just NSN Parts. With this catalog, you can find all of the part numbers we have in stock for NSN 5925-01-300-8939, such as GJ3-A3-DU-125-240-1, GJ3-A3-DUW-125-240-1, and others. To learn more about any particular listing we feature, use the “RFQ” buttons provided on this list to access our online quote request forms. By offering our staff details like your target quantity, pricing, and fulfillment timeframe for components, we can best respond with procurement options that suit your requirements.
| Alternative NSN | 5925013008939 |
| Item Name | Circuit Breaker |
| INC Code | 00136 |
| Federal Supply Group (FSG) | Electrical and Electronic Equipment Components |
| Federal Supply Class (FSC) | 5925 Circuit Breakers |
| National Item Identification Number (NIIN) | 01-300-8939 (013008939) |
| NCB Code | USA (01) |
| Manufacturer | Eaton Corporation, Heinemann Electric Co Inc |
| Part No. | NSN | Item Name | QTY | RFQ |
|---|---|---|---|---|
| GJ3-A3-DU-125-240-1 | 5925-01-300-8939 | circuit breaker | Avl | RFQ |
| GJ3-A3-DUW-125-240-1 | 5925-01-300-8939 | circuit breaker | Avl | RFQ |
Characteristics Data of 5925-01-300-8939, 5925013008939 |
|---|
| MRC | Criteria | Characteristic |
|---|---|---|
| AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
| AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 3.812 INCHES MINIMUM AND 3.844 INCHES MAXIMUM |
| AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 4.282 INCHES MINIMUM AND 4.344 INCHES MAXIMUM |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 125.0 AMPERES AC ALL LOCATIONS |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 18000.0 AC ALL LOCATIONS |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 3 TOGGLE |
| CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
| CQJX | NOMINAL THREAD SIZE | 0.190 INCHES |
| CWJK | CASE MATERIAL | PLASTIC |
| TTQY | TERMINAL TYPE AND QUANTITY | 6 THREADED STUD |
| ADAT | BODY WIDTH | 4.469 INCHES MINIMUM AND 4.531 INCHES MAXIMUM |
| APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| CPRQ | RESET METHOD | MANUAL |
| CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE,TWO,AND THREE LINKED |
| ADAQ | BODY LENGTH | 7.094 INCHES MINIMUM AND 7.156 INCHES MAXIMUM |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 5.968 INCHES MINIMUM AND 6.030 INCHES MAXIMUM |
| AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.469 INCHES MINIMUM AND 1.531 INCHES MAXIMUM |
| AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.469 INCHES MINIMUM AND 1.531 INCHES MAXIMUM |
| AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
| AJEC | BOSS HEIGHT | 0.188 INCHES MINIMUM AND 0.250 INCHES MAXIMUM |
| AKPX | POLE QUANTITY | 3 |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 6 THREADED HOLE |
| CMLP | THREAD QUANTITY PER INCH | 32 |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS |
| CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
| CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 20.000 MINIMUM AT 200 PCT AND 120.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
| FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
| THSD | THREAD SERIES DESIGNATOR | UNF |
Get More Relevant NSN For NSN 5925-01-300-8939, 5925013008939 |
||||
|---|---|---|---|---|
| 5905-00-000-0136 (5905000000136) | 5905-00-001-2573 (5905000012573) | 5905-00-001-2812 (5905000012812) | 5905-00-001-2813 (5905000012813) | |
| 5905-00-001-2814 (5905000012814) | 5905-00-001-2815 (5905000012815) | 5905-00-001-2818 (5905000012818) | 5905-00-001-2819 (5905000012819) | |
| 5905-00-001-2821 (5905000012821) | 5905-00-001-2822 (5905000012822) | 5905-00-001-2826 (5905000012826) | 5905-00-001-2827 (5905000012827) | |
NSN 5925013008939 serves to represent parts that meet similar enough criteria to be grouped under a single identifier. NSNs are part of the National Stock Number system, where unique 13-digit codes are assigned to material items of supply by NATO countries in order to simplify supply-chain management and procurement.
On our website, we carry NSN 5925013008939 parts from manufacturers like Eaton Corporation, Heinemann Electric Co Inc, and others.
Offerings on our NSN 5925013008939 catalog are traceable back to various manufacturers through CAGE Codes like 74193, L3330, and others.
Part numbers we carry that are listed with the NSN 5925013008939 include GJ3-A3-DU-125-240-1, GJ3-A3-DUW-125-240-1, and others.
Every NSN is made up of separate elements that provide information on a particular part. For NSN 5925013008939, key details within the number include its:
The Item Name Code (INC) of NSN 5925013008939 is 00136, such data providing additional classification details for cross referencing offerings.
![]() |
AS9120B and ISO 9001:2015 |
![]() |